Product Overview
The Huawei ETP4890-A2 is an AC/DC embedded power system designed for access networks, transmission networks and enterprise communication equipment. Configured with 1U 15 A or 30 A high-efficiency rectifier modules, it delivers a rated 90 A output (4.8 kW maximum) and installs in standard 19-inch or 21-inch racks at just 2U in height.
The system accepts an extremely wide 85-300 VAC input range, including 220 VAC single-phase and 220/380 VAC three-phase supplies, and outputs adjustable 42-58 VDC with a 53.5 VDC default. Rectifiers and the SMU01A/B/C monitoring unit are fully hot-swappable, and a rectifier dormancy function raises overall system efficiency at partial load.
Natural cooling eliminates fans and associated maintenance, and the front-cabling, front-maintenance architecture suits shallow cabinets. Intelligent battery management and protection extend battery lifespan, while environmental monitoring and remote management are supported through dry contacts, serial interfaces or Ethernet. The system is rated IP20 and documented to IEC 60950-1.
Key Features
- 2U embedded power system, 90 A rated / 4.8 kW maximum output
- Wide 85-300 VAC input, 220 VAC single-phase or 220/380 VAC three-phase
- Hot-swappable 15 A / 30 A rectifiers (R4830G1 up to 96% max efficiency)
- Natural cooling with front cabling and front maintenance
- Intelligent battery management and rectifier dormancy for efficiency
- IP20; IEC 60950-1; remote management via dry contact, serial or Ethernet
Specifications
| Parameter | Value |
|---|---|
| Capacity | 4.8 kW maximum / 90 A rated output |
| Voltage | AC input 85-300 Vac (220 Vac single-phase, 220/380 Vac three-phase, or 110 Vac dual-live-wire); DC output 42-58 Vdc, default 53.5 Vdc |
| Dimensions | 482.6 mm (W) x 255 mm (D) x 86.1 mm (2U H) |
| Weight | 10 kg or less (fully loaded) |
| Operating Temperature | -40C to +70C (system can run 8 hours at +70C) |
| Efficiency | Rectifiers up to 96% max (R4830G1 greater than 95% from 25-100% load) |
| Protection | IP20; IEC 60950-1/GB 4943; battery breaker 1 x 80 A; BLVD 1 x 10 A + 1 x 30 A + 2 x 40 A |
| Other | Natural cooling; 19/21-inch installation; front inlet/outlet cabling; SMU01A/B/C controller with LCD; RS232/RS485/FE communication |
Request Specifications & Quote
Our sales engineering team provides full specifications, pricing, and configuration support within 24 hours.
Contact Us for Specifications