48V Rectifier Module Cross Reference Chart: Huawei, Vertiv, Eltek, ZTE & Delta Equivalents

September 14, 2026 ·

When a telecom DC plant needs a spare rectifier, a discontinued module must be replaced, or a tender requires multi-brand sourcing, engineers need a fast way to match one vendor’s 48V rectifier module against the alternatives. This cross-reference chart maps the mainstream 48V rectifier modules from Huawei, Vertiv (Emerson), Eltek (now part of Eaton), ZTE and Delta by power class, based on published specifications.

Important: a cross-reference means a power-class equivalent — same voltage class and comparable output power. It does not automatically mean form-fit-function interchangeability. Always verify shelf dimensions, rectifier slot width, monitoring protocol (CAN vs RS485) and controller compatibility before swapping brands inside one power system.

Quick Cross Reference — 3000 W Class

The 3000 W module is the workhorse of modern -48V telecom DC plants:

Brand Module Output Power Max Current AC Input Monitor Notes
Huawei R4850N1 3000 W (2900 W @176–300 VAC) 50 A 85–300 VAC RS485 ≥96% efficiency, −40 to +75 °C
Huawei R4850N2 3000 W 50 A 85–300 VAC CAN 40.8 × 105 × 281 mm
Huawei R4850G6 3000 W 50 A 85–300 VAC CAN bus ≥96%, ≤2 kg
Vertiv R48-3000E3 3000 W 62.5 A max 42–58 VDC adj. CAN e3 platform, fits NetSure 731 A41/A91
Eltek Flatpack2 48/3000 HE (241119.105) 3000 W 85–300 VAC class CAN HE platform, parallel operation
Eltek Flatpack2 48/3000 HE (241119.903) 3000 W 80–300 VAC / DC input CAN 53.5 VDC default output
ZTE ZXD2400 V4.6 2400 W rated / 3195 W max 50 A 80–300 VAC class Digital control For ZXDU58 / ZXDU68 systems
Delta DPR48/50C 3000 W 50 A class 90–300 VAC class Digital control Active PFC, parallel operation
Delta DPR-3000B-48 (ESR-48/60AA) 3000 W 60 A 90–300 VAC class Digital control ESR 48V systems

Product pages: Huawei R4850N1 · R4850N2 · Vertiv R48-3000E3 · Eltek Flatpack2 48/3000 HE · Delta DPR48/50C

2000 W Class Cross Reference

Brand Module Output Power Max Current Notes
Vertiv R48-2000e3 2000 W e3 platform, CAN, for NetSure 531/731
Eltek Flatpack2 48/2000 HE (241115.105) 2000 W 41.7 A max 2U shelf hosts up to 4 modules
Eltek Flatpack2 48/2000 HE (241115.705) 2000 W 48/60 VDC wide-output variant
Delta DPR48/50-D-DCE 2880 W 56 A 90–300 VAC class wide input

Product pages: Vertiv R48-2000e3 · Eltek Flatpack2 48/2000 HE · Delta DPR48/50-D-DCE

1000 W Class Cross Reference

Brand Module Output Power Notes
Vertiv R48-1000e3 1000 W e3 platform, CAN monitoring, PF ≥ 0.99
Delta ESR-48/30DD 30 A ESR 48V systems
Delta ESR-4830D 30 A ESR 48V systems

Product pages: Vertiv R48-1000e3 · Delta ESR-48/30DD

System-Level Cross Reference (Embedded DC Plants)

Replacing a module usually means staying inside one system family. These embedded systems are power-class equivalents at the 200 A / 12 kW level:

Brand System Output Rectifier Support Controller
Huawei ETP48200-C5A1 / C7A1 200 A 4 × R4850 series (50 A) hot-swap Digital monitoring
Vertiv NetSure 731 A41-S1 / S2 200 A / 12 kW R48-3000e3 hot-swap M225 / M830B, RS232/RS485/Ethernet
Vertiv NetSure 731 A91-S3 450 A 9 × R48-3000e3 Intelligent battery management
ZTE ZXDU68 B201 200 A ZXD2400 V4.6 class
ZTE ZXDU68 B301 300 A ZXD2400 V4.6 class

Product pages: Huawei ETP48200-C5A1 · Vertiv NetSure 731 A41-S1 · ZTE ZXDU68 B201

Compatibility Notes Before You Swap

  1. Monitoring protocol mismatch. Huawei R4850N1 uses RS485 while R4850N2/G6 and the Vertiv e3 and Eltek HE platforms use CAN. A replacement module whose protocol the system controller cannot read will run blind — no alarms, no battery management data.
  2. Slot width and shelf height. Flatpack2 HE modules and R48-series e3 modules have different mechanical footprints; a power-class equivalent is rarely slot-compatible across brands.
  3. Input window differences. Vertiv R48-3500E3 requires 200–277 VAC (no low-line operation), while most others accept 85–300 VAC class wide input. Sites with weak generator supply must keep the wide-input variant.
  4. Redundancy design. All five brands support hot-swap and parallel operation with N+1 redundancy — but never mix rectifier brands inside one shelf; load-sharing logic is vendor-specific.

How BS Comtec Helps

BS Comtec supplies 48V rectifier modules and embedded DC power systems from Huawei, Vertiv (Emerson), Eltek, ZTE and Delta from Singapore stock, MOQ from 1 piece, dispatch within 24–48 hours for in-stock items. Send us your current module part number (or the part number on the nameplate photo) and we will confirm the closest equivalent in stock, with datasheets on request.

Is a cross-reference the same as a drop-in replacement?

No. A cross-reference identifies a power-class equivalent — the same -48V voltage class and comparable output wattage. Mechanical fit, monitoring protocol (CAN vs RS485) and controller compatibility must be verified separately before swapping brands inside one power system.

Which 48V rectifier modules from this chart are still in production?

Currently produced lines include Huawei R4850N2/G6, Vertiv R48-3000E3 and R48-3500E3, Eltek Flatpack2 48/3000 HE, ZTE ZXD2400 V4.6 and Delta DPR48/50C. Older units such as the R48-2000e3 remain widely deployed and are available as spare modules.

Can I mix rectifier brands in one power shelf?

No. Load-sharing, hot-swap handshaking and controller protocols are vendor-specific. Each shelf must run one brand and one module family; the cross-reference chart is for system-level replacement planning, not shelf mixing.

What information does BS Comtec need to confirm an equivalent module?

The module part number or nameplate photo, the power shelf or system model it slots into, and your AC input conditions. With these three items BS Comtec can confirm the closest in-stock equivalent and provide the datasheet.