📧 longyouvip@gmail.com 📞 +86 135 8237 6986 🌍 Serving 89+ Countries
OEM DC Cabinet Air Conditioner 300-5000W 48VDC IP55 for Telecom Outdoor Cabinets (MPD Series)

OEM DC Cabinet Air Conditioner 300-5000W 48VDC IP55 for Telecom Outdoor Cabinets (MPD Series)

MPD Series DC cabinet air conditioner is a variable-frequency enclosure cooling unit powered directly by 48VDC. Designed for telecom outdoor cabinets, solar-powered sites and energy storage enclosures, it covers 300-5000 W cooling capacity with IP55 protection, -40 to +55 °C…
  • ✔ Factory-fresh original equipment & authentic serials
  • ✔ Global rapid dispatch with export sea/air packing
  • ✔ 24h engineering consultation & BOM customization
  • ✔ Full manufacturer warranty & spare modules in stock
⚡ Instant Engineer & Sales Quotation
Jack Sales Manager
WhatsApp: +86 135 8237 6986
Email: longyouvip@gmail.com
Ethan Sales Manager
WhatsApp: +86 157 3227 3917
Email: zy123321123456@gmail.com

Product Overview

MPD Series DC cabinet air conditioner is a variable-frequency enclosure cooling unit powered directly by 48VDC. Designed for telecom outdoor cabinets, solar-powered sites and energy storage enclosures, it covers 300-5000 W cooling capacity with IP55 protection, -40 to +55 °C operating range and RS485 remote monitoring. Because it draws power from the same -48VDC bus that feeds the telecom load, it integrates naturally with 48V power systems such as the Huawei TP48 series outdoor power cabinets and MTS9512A integrated cabinets.

OEM DC cabinet air conditioner 48VDC wall-mounted unit

Key Features

  • 48VDC variable-frequency input: direct connection to the telecom -48VDC bus, better energy efficiency than fixed-speed units
  • Wide temperature range: reliable operation from -40 °C to +55 °C, with optional heater (300-500 W) for cold climates
  • IP55 protection: dust-tight and water-jet resistant, suitable for outdoor pole-mounted and ground cabinets
  • Eco refrigerant: R134a, no ozone depletion potential
  • Industrial-grade components:知名品牌 compressor and fan parts for long service life
  • Remote monitoring: RS485 interface plus multi-function alarm output for NOC integration

Model Range & Specifications

Model Cooling Capacity (W) Heater (W, optional) Power (W) Noise dB(A) Weight (kg)
MPD0300 300 300 120 54 7
MPD0500 500 300 150 54 12.5
MPD1000 1000 500 320 64 24
MPD1500 1500 500 430 64 25
MPD2000 2000 500 570 64 36
MPD3000 3000 500 1140 65 60
MPD4000 4000 500 1280 65 64
MPD5000 5000 500 1450 70 75

All models operate on 48VDC input with R134a refrigerant and IP55-rated enclosures. Dimensions range from 370×219×133 mm (MPD0300) to 1401×671×310 mm (MPD5000); OEM dimensions are available on request.

How to Select Cooling Capacity

Sizing a cabinet air conditioner starts with the heat load inside the enclosure: add the heat dissipated by rectifiers, batteries, inverters and other equipment, then include solar radiation gain on the cabinet surface (typically 500-1000 W for a cabinet in full sun). A common rule for telecom cabinets is to install a cooling unit rated at 1.2-1.5 times the calculated internal heat load. For a typical 5G outdoor cabinet with 2-3 kW of equipment heat, the MPD3000 or MPD4000 is the usual choice; small pole-mounted cabinets with under 1 kW of load use MPD0300-MPD1000.

MPD Series vs. Fixed-Speed Enclosure Coolers

Compared with fixed-frequency AC-powered enclosure coolers, the MPD Series variable-speed compressor modulates output to match the actual heat load instead of cycling on/off. This keeps cabinet temperature more stable, reduces compressor start-stop wear and cuts energy consumption noticeably at partial load — an advantage that compounds across fleets of hundreds of cabinets. The 48VDC input also removes the need for a separate AC distribution or inverter inside power-system cabinets.

Applications

  • 5G base station outdoor cabinets and integrated equipment cabinets
  • Solar and hybrid-powered telecom sites with -48VDC systems
  • Energy storage enclosures and battery cabinets
  • Outdoor distribution and cross-connection cabinets
  • Edge data center and FTTx outdoor equipment enclosures
DC cabinet air conditioner installed on outdoor telecom cabinet

Installation Notes

The MPD Series mounts on the cabinet side door or wall panel with a standard mounting flange; units from MPD0300 to MPD2000 fit most standard 19-inch and telecom outdoor cabinets. Keep at least 300 mm clearance around the condenser grille for airflow, and route the RS485 wiring to the site monitoring unit so alarm outputs reach the network management system. For sites below -20 °C, order the optional heater and enable low-temperature startup settings.

Product Views

DC cabinet air conditioner rear view with mounting bracket
DC cabinet air conditioner with digital control panel

Frequently Asked Questions

Q: Can the MPD Series run directly from a telecom -48VDC battery bus without a separate inverter?

A: Yes. The MPD Series accepts 48VDC input directly and connects to the same -48VDC bus that powers rectifiers and telecom loads, eliminating the inverter and its conversion losses. This is the main reason it fits 48V telecom power cabinets and solar-powered sites.

Q: How many MPD units do I need for a cabinet with 5 kW of equipment heat?

A: A single MPD5000 (5000 W) covers about 4 kW of internal heat load after derating for solar gain, so two MPD3000 units or one MPD5000 plus a heat-exchanger assist are typical for 5 kW cabinets. Share your cabinet heat load list with BScomtec for a sized recommendation.

Q: Does the unit support integration with site monitoring systems?

A: Yes. Every MPD model provides RS485 communication and multi-function alarm output (high/low temperature, compressor fault, sensor failure), which integrates with standard telecom site controllers and NOC platforms.